High voltage and current ,
High AC current: current transformer phase displacement
:
0 rad to 3.14 rad
Current transformer, current transducer, merging unit
Absolute expanded uncertainty
:
5.0E-2 mrad to 0.2 mrad
Uncertainty table
{"row_1":{"col_1":"Output<br>","col_2":"Frequency<br>","col_3":"Input current<br>","col_4":"Uncertainty [mrad]<br>"},"row_2":{"col_1":"Voltage or current<br>","col_2":"45 Hz to 65 Hz","col_3":"10 mA to 8000 A","col_4":"0.05<br>"},"row_3":{"col_1":"Voltage or current<br>","col_2":"65 Hz to 250 Hz","col_3":"10 mA to 500 A","col_4":"0.07<br>"},"row_4":{"col_1":"Voltage or current<br>","col_2":"250 Hz to 300 Hz<br>","col_3":"10 mA to 250 A","col_4":"0.07"},"row_5":{"col_1":"Voltage or current<br>","col_2":"300 Hz to 350 Hz","col_3":"10 mA to 100 A","col_4":"0.07"},"row_6":{"col_1":"Voltage or current<br>","col_2":"350 Hz to 1000 Hz","col_3":"10 mA to 10 A","col_4":"0.1"},"row_7":{"col_1":"Digital<br>","col_2":"45 Hz to 65 Hz","col_3":"10 mA to 20 A","col_4":"0.05"},"row_8":{"col_1":"Digital<br>","col_2":"65 Hz to 500 Hz","col_3":"10 mA to 20 A","col_4":"0.1<br>"},"row_9":{"col_1":"Digital<br>","col_2":"500 Hz to 1000 Hz","col_3":"10 mA to 20 A","col_4":"0.2"}}
Comparison with reference standard
Frequency : 45 Hz to 1000 Hz
Input current : 10 mA to 8 kA
Output current : 10 mA to 20 A
Output voltage : 10 mV to 500 V
Digital output : according to IEC 61869-9
Approved on 21 October 2024
Institute service identifier : HV58n
CMC ID :
EURAMET-EM-FI-00000E75-6